Case: T05FR01157
Case Details
Entered Date:
07/25/2005
Applicant:
DND NEFFSON CO
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR01157
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/25/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 305.1 The transformer located in the stockroom shall be seperated from combustibles |
07/25/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage in the stockroom shall be maintained 18 inches below the ceiling |
07/25/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 Stockroom doors shall not be blocked in the open position. Doorstop shall be removed |
07/25/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 The exit sign at the stockroom exit shall be repaired |
07/25/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 The exit corridor at the rear of the store shall be maintained clear. |
07/25/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.6 The flush bolts on the rear exit shall be removed. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01157
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/07/2005 | INSP - FULL | TKNAPP | Approved |