Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR01157
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
07/25/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 305.1 The transformer located in the stockroom shall be seperated from combustibles
07/25/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage in the stockroom shall be maintained 18 inches below the ceiling
07/25/2005 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 Stockroom doors shall not be blocked in the open position. Doorstop shall be removed
07/25/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The exit sign at the stockroom exit shall be repaired
07/25/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 The exit corridor at the rear of the store shall be maintained clear.
07/25/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.6 The flush bolts on the rear exit shall be removed.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01157
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/07/2005 INSP - FULL TKNAPP Approved