Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

07/21/2005

Applicant:

DND NEFFSON CO

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR01139
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
07/21/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 305.1 Clearance shall be maintained between the transformer and combustibles
07/21/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 The electrical panel in the stockroom shall be accessible
07/21/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 The portable fire extinguishers shall be inspected annually
07/21/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1013.4.1 Ailes shall be maintained in the stockroom at 28 inches wide
07/21/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The exit sign at the mall exit shall be repaired so that it remains lit

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01139
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/07/2005 INSP - FULL TKNAPP Approved