Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

07/21/2005

Applicant:

DND NEFFSON CO

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR01137
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
07/21/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage in the stockroom shall be located 18 inches below the level of the sprinkler heads.
07/21/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 The sprinkler head located in the west stockroom shall be repaired so that its cover is not held in place with tape.
07/21/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 The exit path in the stockroom leading to the rear exit shall be clear

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01137
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/08/2005 INSP - FULL TKNAPP Approved