Case Details

Status:

REFERRED

Type:

INSPECTION
Address:

Entered Date:

07/20/2005

Applicant:

CORFINIUM HOLDINGS LLC

Description:

Inspection

Outstanding Inspections

Case Number: T05FR01123
Case Status: REFERRED
Case Description: INSPECTION
Total Outstanding Inspections - 23
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
07/19/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 102.6- No building or structure shall be used or occupied...until the building official has issued a Certificate of Occupancy. It shall be posted in a conspicuous location. Applied on 3-01-05 T05OT00444
07/19/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 105.6.17- An operational permit is required to use, store or handle...Class III-B liquids in excess of 60 gallons outside a building.
07/19/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 304.3.1- Oily rags shall be stored in listed disposal container with self-closing lid.
07/19/2005 VIOL - EMERGENCY PLAN/PREPARE JLANGEJA Violation TFC 407.2- Material Safety Data Sheets for all hazardous materials shall be readily available on the premises.
07/19/2005 VIOL - FIRE SERVICE FEATURES JLANGEJA Violation TFC 505.1- Address numbers shall be in accordance with Pima County Address display requirements.
07/19/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Electrical hazards shall be abated. Receptacle on West wall shall be replaced.
07/19/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.4.2- Relocatable power taps shall be directly connected to a permanently installed receptacle.
07/19/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. behind counter 2. through front door to outside light 3. outside East bay
07/19/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5.3- Extension cords shall be maintained in good condition without splices, deterioration or damage.
07/19/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.6- Open junction boxes and open wiring splices shall be prohibited. 1. W wall of bay 1 2. overhead lights in bay 2 3. overhead sleeves in bay 2 4. open j-box on 5th wheel trailor 5. service panel needs blank cover (N wall)
07/19/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers shall be serviced annually and have a current service tag attached.
07/19/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.1- Fire extinguishers shall be a minimum of 2A:20-B:C with a maximum travel distance of 75 feet.
07/19/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.7- Fire extinguishers shall be installed on hangers or brackets.
07/19/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1008.1.8- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
07/19/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1008.1.8.3- A lock or latch is permitted provided that a readily visible durable sign is posted on the egress side of the door stating "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED". The letters shall be 1" on a contrasting background.
07/19/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.3.1.4- The person, firm or corporation responsible for an unauthorized discharge shall institute and complete all actions necessary to remedy the effects of such discharge, whether sudden or gradual, at no cost to the jurisdiction. 1. clean up needed around storage tanks 2. clean up neede behind bay
07/19/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.5- Visible hazard identification signs shall be attached to portable tanks specifying the contents within.
07/19/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.5.1- Individual containers, cartons and packages shall be conspicuously marked or labeled in an approved manner. Several throughout.
07/19/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.7.1- Smoking shall be prohibited and "NO SMOKING" signs shall be provided in all rooms or areas where flammable or combustible materials are stored, dispensed or used.
07/19/2005 VIOL - COMPRESSED GASES JLANGEJA Violation TFC 3003.2- Compressed gas cylinders shall be marked.
07/19/2005 VIOL - COMPRESSED GASES JLANGEJA Violation TFC 3003.3- Compressed gas cylinders shall be secured against accidental dislodgement.
07/19/2005 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation TFC 3404.3.1.1- Only approved containers shall be used for storage of flammable or combustible liquids.