Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

07/15/2005

Applicant:

WILLIAMS MICHAEL M & LAUER-WILLIAMS JEANNE TR

Description:

Inspection

Outstanding Inspections

Case Number: T05FR01098
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
07/14/2005 VIOL - PRECAUTION AGAINST FIRE JVALENZU Violation 315.2.1 - storage shall be maintained 2 feet or more below the ceiling in non-sprinklered buildings. * throughout warehouse
07/14/2005 VIOL - FIRE SERVICE FEATURES JVALENZU Violation 505.1 - buildings shall have address numbers in accordance with Pima County requirements, plainly legible, visible from the street fronting the property.
07/14/2005 VIOL - BUILDING SVCS & SYSTEMS JVALENZU Violation 605.3 - a working space of not less than 30''W x 36''D x 78''H shall be provided in front of electrical service equipment * breaker panel south wall
07/14/2005 VIOL - FIRE PROTECTION SYSTEMS JVALENZU Violation 906.1 - portable fire extinguishers shall be serviced annually. * two in warehouse
07/14/2005 VIOL - MEANS OF EGRESS JVALENZU Violation 1008.1.8 - egress doors shall be readily openable from the egress side without the use of a key * remove the deadbolt on southwest warehouse door
07/14/2005 VIOL - MEANS OF EGRESS JVALENZU Violation 1008.1.8.3 - a readily visible sign shall be posted on the inside of the front door stating ''THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED'' The letters shall be 1 inch high on contrasting background.

Completed Inspections

Case Status: FIELD
Case Number: T05FR01098
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/15/2005 VIOL - ADMINISTRATION JVALENZU Approved