Case: T05FR01072
Case Details
Entered Date:
07/14/2005
Applicant:
DND NEFFSON CO
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR01072
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/14/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage located in stockroom shall be 18 inches below sprinkler heads. |
07/14/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The missing celing tile in the office area shall be replaced. |
07/14/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.2 The stockroom door at the exit from the sales floor shall not be blocked open. |
07/14/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 The portable fire extinguisher located at the counter and in the stockroom shall be inspected annually |
07/14/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 The southeast stockroom exit door shall be readily openable without a key from the egress side. |
07/14/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 The exit sign located at the stockroom exit shall be repaired so that it remains lit at all times. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01072
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/07/2005 | INSP - FULL | TKNAPP | Approved |