Full Inspection

Outstanding Inspections

Case Number: T05FR01043
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date Description Inspector Results Comments
07/07/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 The electrical panel at the east room of the west building shall have blanks installed where breakers are missing.
07/07/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 The extinsion cords in the east building shall not be used as permanent wiring.
07/07/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8 The exit door of the northwest room shall not have a lock that requires a key.
07/07/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.3 A readily visible sign stating This door to remain unlocked when building is occupied" shall be installed on the west exit of the west building.
07/07/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 Exit door in northwest room shall be continuously maintained free from obstructions.
07/07/2005 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1503.2.6 No smoking signs shall be posted in all rooms.
07/07/2005 VIOL - HAZARDOUS MATERIALS,GEN TKNAPP Correction Required 2703.4 MSDS sheets shall be readily available for all hazardous materials on the premises.
07/07/2005 VIOL - HAZARDOUS MATERIALS,GEN TKNAPP Correction Required 2703.5 Visible hazard identification signs shall be posted at all entrances to the building where painting is done.
07/07/2005 VIOL - HAZARDOUS MATERIALS,GEN TKNAPP Correction Required 2703.5.1 Fifty five gallon drums that are empty shall be labled empty.
07/07/2005 VIOL - FLAMMABLE LIQUIDS TKNAPP Correction Required 3404.3.4.4 Flammable liquids shall be stored in a flammable liquid storage cabinet.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01043
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/29/2005 INSP - FULL TKNAPP Approved