Case: T05FR01034
Case Details
Entered Date:
07/06/2005
Applicant:
RANDOLPH PLAZA LLC
Description:
fire inspection
Outstanding Inspections
Case Number: T05FR01034
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
07/06/2005 | VIOL - PRECAUTION AGAINST FIRE | JDAVIS | Correction Required | do not store combustibles in electrical rooms do not store stock within 18 inches of sprinkler heads |
07/06/2005 | VIOL - BUILDING SVCS & SYSTEMS | JDAVIS | Correction Required | blocking electrical panel 610; clean and repair hood missing electrial coverplates improper extension cord use |
07/06/2005 | VIOL - FIRE RESIST.RATED CONST | JDAVIS | Correction Required | maintain fire resistive construction: ceiling tiles repair self--closure |
07/06/2005 | VIOL - FIRE PROTECTION SYSTEMS | JDAVIS | Correction Required | mount extinguishers test sprinkler system annually clear storage around riser |
07/06/2005 | VIOL - MEANS OF EGRESS | JDAVIS | Correction Required | maintain aisle width 28 inches remove the signs on all doors that say, "15 second delay" |
07/06/2005 | VIOL - COMPRESSED GASES | JDAVIS | Correction Required | 3003.3 secure compressed gas cylinders |