Case: T05FR01003
Case Details
Entered Date:
06/28/2005
Applicant:
DND NEFFSON CO
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR01003
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/28/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 305.1 Clearance shall be maintained between the transformer and combustibles. |
06/28/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 Electrical panels in the stockroom shall have clear access. |
06/28/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 703.2 The fire rated door at the north end of the sales floor that was removed, shall be replaced. |
06/28/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The missing ceiling in the stockroom shall be replaced. |
06/28/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1013.4.1 Aisles in the stockroom shall be maintained. 28 inches wide |
06/28/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 The northwest stockroom exit shall not be obstructed. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01003
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/13/2005 | INSP - FULL | TKNAPP | Approved |