Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR01003
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
06/28/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 305.1 Clearance shall be maintained between the transformer and combustibles.
06/28/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 Electrical panels in the stockroom shall have clear access.
06/28/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 703.2 The fire rated door at the north end of the sales floor that was removed, shall be replaced.
06/28/2005 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 The missing ceiling in the stockroom shall be replaced.
06/28/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1013.4.1 Aisles in the stockroom shall be maintained. 28 inches wide
06/28/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 The northwest stockroom exit shall not be obstructed.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01003
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/13/2005 INSP - FULL TKNAPP Approved