Case Number: T05FR01000
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
06/28/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 305.1 Clearance shall be maintained between transformer and combustibles.
06/28/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage in stockroom shall be 18 inches below sprinkler heads.
06/28/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 Access shall be maintained to electrical panels.
06/28/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 The north rear exit shall not be obstructed.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01000
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/13/2005 INSP - FULL TKNAPP Approved