Case Details

Status:

REFERRED

Type:

INSPECTION
Address:

Entered Date:

06/28/2005

Applicant:

MALONE RALPH A TR & MALONE FLORADEL TR

Description:

Inspection

Outstanding Inspections

Case Number: T05FR00995
Case Status: REFERRED
Case Description: INSPECTION
Total Outstanding Inspections - 15
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
06/28/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 105.6.17- An operational permit is required to store, handle or use Class III-B liquids in excess of 60 gallons outside. Contact Diane Gamble @ 791-4502 for permit.
06/28/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC102.6- No building or structure shall be used or occupied...until the building official has issued a Certificate of Occupancy.
06/28/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.1- Storage of combustibles shall be maintained 2 feet or more below the ceiling in a non-sprinklered building.
06/28/2005 VIOL - EMERGENCY PLAN/PREPARE JLANGEJA Violation TFC 407.2- MSDSs for all hazardous materials shall be readily available on the premises.
06/28/2005 VIOL - FIRE SERVICE FEATURES JLANGEJA Violation TFC 504.2- Exterior doors that have been rendered non-functional and have the appearance of a functional door from the exterior shall have a sign affixed to the exterior side stating "THIS DOOR BLOCKED". Letters shall be at least 6" in height on a contrasting background.
06/28/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Electrical hazards shall be abated. Surge protector has damaged sheath and shall be replaced.
06/28/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.6- Open junction boxes and open wiring splices shall be prohibited. (changing room)
06/28/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers shall be serviced annually. (outside)
06/28/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.7- Fire extinguishers shall be mounted on hangers or brackets and anchored securely. (x 2)
06/28/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1011.1- Exit sign is not required and shall be removed.
06/28/2005 VIOL - WELDING & OTHER HOT WRK JLANGEJA Violation TFC 2604.1.1- Hot work areas shall not contain combustibles or shall be provided with appropriate shielding to prevent sparks, slag or heat from igniting exposed combustibles.
06/28/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.5.1- Individual containers shall be conspicuously marked or labeled in an approved manner. (55 gallon drum outside)
06/28/2005 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation TFC 3403.1.1- Class I-Div II electrical shall be used within 5 feet of any edge of a solvent tank.
06/28/2005 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation TFC 3405.3.6.2.7- Solvent machines shall be maintained in accordance with their listing. Power to pump shall be from a GFCI curcuit.