Case: T05FR00995
Case Details
Entered Date:
06/28/2005
Applicant:
MALONE RALPH A TR & MALONE FLORADEL TR
Description:
Inspection
Outstanding Inspections
Case Number: T05FR00995
Case Status: REFERRED
Case Description: INSPECTION
Total Outstanding Inspections - 15
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
06/28/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 105.6.17- An operational permit is required to store, handle or use Class III-B liquids in excess of 60 gallons outside. Contact Diane Gamble @ 791-4502 for permit. |
06/28/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC102.6- No building or structure shall be used or occupied...until the building official has issued a Certificate of Occupancy. |
06/28/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.1- Storage of combustibles shall be maintained 2 feet or more below the ceiling in a non-sprinklered building. |
06/28/2005 | VIOL - EMERGENCY PLAN/PREPARE | JLANGEJA | Violation | TFC 407.2- MSDSs for all hazardous materials shall be readily available on the premises. |
06/28/2005 | VIOL - FIRE SERVICE FEATURES | JLANGEJA | Violation | TFC 504.2- Exterior doors that have been rendered non-functional and have the appearance of a functional door from the exterior shall have a sign affixed to the exterior side stating "THIS DOOR BLOCKED". Letters shall be at least 6" in height on a contrasting background. |
06/28/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.1- Electrical hazards shall be abated. Surge protector has damaged sheath and shall be replaced. |
06/28/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open junction boxes and open wiring splices shall be prohibited. (changing room) |
06/28/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be serviced annually. (outside) |
06/28/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.7- Fire extinguishers shall be mounted on hangers or brackets and anchored securely. (x 2) |
06/28/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1011.1- Exit sign is not required and shall be removed. |
06/28/2005 | VIOL - WELDING & OTHER HOT WRK | JLANGEJA | Violation | TFC 2604.1.1- Hot work areas shall not contain combustibles or shall be provided with appropriate shielding to prevent sparks, slag or heat from igniting exposed combustibles. |
06/28/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.5.1- Individual containers shall be conspicuously marked or labeled in an approved manner. (55 gallon drum outside) |
06/28/2005 | VIOL - FLAMMABLE LIQUIDS | JLANGEJA | Violation | TFC 3403.1.1- Class I-Div II electrical shall be used within 5 feet of any edge of a solvent tank. |
06/28/2005 | VIOL - FLAMMABLE LIQUIDS | JLANGEJA | Violation | TFC 3405.3.6.2.7- Solvent machines shall be maintained in accordance with their listing. Power to pump shall be from a GFCI curcuit. |