Case: T05FR00966
Case Details
Entered Date:
06/24/2005
Applicant:
LA PALOMA FAMILY SERVICES
Description:
Full Fire inspection BHL for 9
Outstanding Inspections
Case Number: T05FR00966
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2005 | INSP - FULL | SHIGGINB | Violation | this is a single family residence that was converted to a R4 group home lic for 9 under behavior health |
| 06/27/2005 | VIOL - ADMINISTRATION | SHIGGINB | Violation | TFC 2003. 102.3 Change of use or occupancy. A new C of O is requeired if the use of a building is changed. 1. Contact DS at 791 5550 and get a new C of O |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00966
Case Description: INSPECTION
Total Completed Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2005 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | TFC 2003 1026.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such,occupancies require two or more means of egress: 1. Place emergency lighting as to light the exit pathway from any portion of the building. Emergency lighting must have battery backup. |
| 06/27/2005 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | TFC 2003 1027.5 Emergency escape openings. Required emergency escape openings shall be maintained in accordance with the code Do not block emergency exits with bedroom furniture. 1. Move dresser from in front of window in east middle bedroom. |
| 06/27/2005 | VIOL - PRECAUTION AGAINST FIRE | SHIGGINB | Approved | TFC 2003. 310.8 310.8 Hazardous environmental conditions. When the fire code official determines that hazardous environmental conditions necessitate controlled use of smoking materials, the ignition or use of such materials in mountainous, brush-covered or forest-covered areas or other designated areas is prohibited except in approved designated smoking areas. 1. Provide a designated smoking area out side the building with ash tray and a sign that reads " Designated Smoking area". This area must be away from the building. Please review your state regs. regaurding designated smoking areas also. |
| 06/27/2005 | VIOL - PRECAUTION AGAINST FIRE | SHIGGINB | Approved | TFC 2003 316.1 General. Heating appliances shall be installed and maintained in accordance with their listing and the City of Tucson Building, Electrical, and Mechanical codes. 1. Combustable air vents are requiered in hot water closet. 2. Clean hot water closet of leaves and keep leaves from entering in the future. 3. Do not store combustables in hot water closet. 4. Fix drywall at base of hot water closet |
| 06/27/2005 | VIOL - PRECAUTION AGAINST FIRE | SHIGGINB | Approved | TFC 2003 304.1.2 Vegetation. Weeds, grass, vines or other growth that is capable of being ignited and endangering property. 1. Clean weeds in alley between property lines |
| 06/27/2005 | VIOL - BUILDING SVCS & SYSTEMS | SHIGGINB | Approved | TFC 2003 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. All electrical wire that is on the outside of the home must be protected from the elements by being placed in conduet. 1. Over the back door, the lights on the NE corner, and wires that are around the dryer shelter. 2. Lights on the NW corners. |