Case Details

Status:

REFERRED

Type:

INSPECTION
Address:

Entered Date:

06/23/2005

Applicant:

STOLL RONALD E & PATRICIA A

Description:

Inspection

Outstanding Inspections

Case Number: T05FR00960
Case Status: REFERRED
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
06/23/2005 VIOL - ADMINISTRATION JLANGEJA Violation
06/23/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 102.6- Design and construction shall comply with the International Building Code. Required separation between a "B" occupancy and an "S-1" is 3 hours of a fire resistive rated construction type.
06/23/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 102.6- No building or structure shall be occupied ...until the building official has issued a Certificate of Occupancy.
06/23/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2- Storage of combustibles shall be orderly. Office filled with combustibles shall be accessible.
06/23/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.1- Storage of combustibles shall be maintained at least 2 feet from the ceiling in a non-sprinklered building.
06/23/2005 VIOL - EMERGENCY PLAN/PREPARE JLANGEJA Violation TFC 407.2- Material Safety Data Sheets for all hazardous materials shall be readily available on the premises.
06/23/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Identified electrical hazards shall be abated. The wires shall be terminated in an approved junction box or removed. (S wall in closet)
06/23/2005 VIOL - FIRE RESIST.RATED CONST JLANGEJA Violation TFC 703.1- Fire resistive rated construction shall be maintained. Drywall shall be repaired to maintain separation.
06/23/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1008.1.8.3- A readily visible durable sign on the egress side of the door shall be posted stating "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED". It shall be 1" letters on a contrasting background.