Case: T05FR00960
Case Details
Entered Date:
06/23/2005
Applicant:
STOLL RONALD E & PATRICIA A
Description:
Inspection
Outstanding Inspections
Case Number: T05FR00960
Case Status: REFERRED
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
06/23/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | |
06/23/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 102.6- Design and construction shall comply with the International Building Code. Required separation between a "B" occupancy and an "S-1" is 3 hours of a fire resistive rated construction type. |
06/23/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 102.6- No building or structure shall be occupied ...until the building official has issued a Certificate of Occupancy. |
06/23/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2- Storage of combustibles shall be orderly. Office filled with combustibles shall be accessible. |
06/23/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.1- Storage of combustibles shall be maintained at least 2 feet from the ceiling in a non-sprinklered building. |
06/23/2005 | VIOL - EMERGENCY PLAN/PREPARE | JLANGEJA | Violation | TFC 407.2- Material Safety Data Sheets for all hazardous materials shall be readily available on the premises. |
06/23/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.1- Identified electrical hazards shall be abated. The wires shall be terminated in an approved junction box or removed. (S wall in closet) |
06/23/2005 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | TFC 703.1- Fire resistive rated construction shall be maintained. Drywall shall be repaired to maintain separation. |
06/23/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1008.1.8.3- A readily visible durable sign on the egress side of the door shall be posted stating "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED". It shall be 1" letters on a contrasting background. |