Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

06/20/2005

Applicant:

DND NEFFSON CO

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR00921
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
06/20/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 305.1 Clearance shall be maintained around transformer
06/20/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 Electrical panel shall be accessible
06/20/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit sign at mall exit shall be repaired

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00921
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/20/2005 INSP - FULL TKNAPP Approved