Case: T05FR00915
Case Details
Entered Date:
06/17/2005
Applicant:
DND NEFFSON CO
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00915
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 305.1 Clearance shall be maintained between the electrical transformer and combustible storage. |
06/17/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 The portable fire extinguishers (2) located behind the counter and in the stockroom shall be inspected annually. |
06/17/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1013.4.1 The aisle in the stockroom shall be maintained clear and free from storage. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00915
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/06/2005 | INSP - FULL | TKNAPP | Approved |