Case: T05FR00912
Case Details
Entered Date:
06/17/2005
Applicant:
DND NEFFSON CO
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00912
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 The storage in the stockroom shall be maintained 18 inches below the level of the sprinkler heads. |
06/17/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | The missing ceiling tiles located in the stockroom shall be replaced. |
06/17/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 The 3 portable fire extinguishers located in the stockroom shall be inspected annually. |
06/17/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1013.4.1 Clear aisles shall be maintained in the stockroom. Storage shall not be allowed to block exit access. |
06/17/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 The exit sign located at the mall exit shall be repaired so that it remains lit at all times. |
06/17/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 The exit sign located at the stockroom exit shall be repaired so that it remains lit at all times. |
06/17/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 The exit corridor located at the east side of the store shall be maintained free from obstructions. No storage shall be allowed in this exit corridor. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00912
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/14/2005 | INSP - FULL | TKNAPP | Approved |