Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR00909
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
06/17/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 305.1 Clearance shall be maintained between the electrical transformer and combustibles.
06/17/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage in the stockroom shall be maintained 18 inches below the level of the sprinkler heads.
06/17/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 The electrical panels located in the stockroom shall be accessible.
06/17/2005 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 The missing ceiling tiles located in the stockroom shall be replaced.
06/17/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 906.7 The portable fire extinguisher located in the stockroom shall be installed on a hanger or bracket.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00909
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/20/2005 INSP - FULL TKNAPP Approved