Case: T05FR00909
Case Details
Entered Date:
06/17/2005
Applicant:
DND NEFFSON CO
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00909
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 305.1 Clearance shall be maintained between the electrical transformer and combustibles. |
06/17/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage in the stockroom shall be maintained 18 inches below the level of the sprinkler heads. |
06/17/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 The electrical panels located in the stockroom shall be accessible. |
06/17/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The missing ceiling tiles located in the stockroom shall be replaced. |
06/17/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.7 The portable fire extinguisher located in the stockroom shall be installed on a hanger or bracket. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00909
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/20/2005 | INSP - FULL | TKNAPP | Approved |