Case: T05FR00889
Case Details
Entered Date:
06/16/2005
Applicant:
MARQUEZ AGUSTINE H & DINA M JT/RS
Description:
Inspection
Outstanding Inspections
Case Number: T05FR00889
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 18
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 06/15/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 102.6- No building or structure shall be occupied...until the building official has issued a Certificate of Occupancy. |
| 06/15/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 111.1- Stop Work Order. Whenever the fire code official finds any work regulated by this code being performed in a manner contrary to the provisions of this code or in a dangerous or unsafe manner, the fire code official is authorized to issue a stop work order. ***All spraying of flammable finishes shall cease.*** |
| 06/15/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 313.1- Fueled equipment shall not be stored within a building. |
| 06/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.1- Unprotected wiring shall be prohibited. (paint room) |
| 06/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.4- Extension cords shall not be a substitute for permanent wiring. (office) |
| 06/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.4- Multiplug adapters shall be prohibited. (through wall of hot works area S) |
| 06/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open junction box shall be abated. Receptacle needs cover plate. (office, kitchen) |
| 06/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open wiring splices shall be prohibited. (open wiring outside spray booth) |
| 06/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open wiring splices shall be prohibited. Blanks shall be installed in electrical panel. |
| 06/15/2005 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | TFC 703.1- Fire resistive-rated construction shall be maintained. The door to the flammables shall be a 20 minute fire rated door. The floor shall be repaired. |
| 06/15/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be serviced annually. |
| 06/15/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.7- Fire extinguishers shall be installed on their hanger or bracket. |
| 06/15/2005 | VIOL - FLAMMABLE FINISHES | JLANGEJA | Violation | TFC 1504.6- Spray booths shall be protected by an approved automatic fire extinguishing system. |
| 06/15/2005 | VIOL - WELDING & OTHER HOT WRK | JLANGEJA | Violation | TFC 2604.1.1- Hot works area shall not contain combustibles or shall be provided with appropriate shielding. |
| 06/15/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.2.1- Containers for hazardous materials shall be of an approved type. Container in outside storage shall have a cap. |
| 06/15/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.3- Hazardous materials shall not be released onto the ground.(under air compressors) |
| 06/15/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2704.3- Indoor storage areas shall be provided with mechanical exhaust ventilation. (paint room) |