Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

06/13/2005

Applicant:

DND NEFFSON CO

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR00856
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
06/13/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage in the stockroom shall be maintained 18 inches below the level of the sprinkler heads.
06/13/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 Electrical equipment in the stockroom shall have a clear working space.
06/13/2005 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1The celing tiles in the stockroom that are missing shall be replaced.
06/13/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 The extinguisher at the stockroom shall be inspected.
06/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1013.4.1 The aisles in the stockroom shall be maintained 28 inches wide.
06/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit sign in northeast corner of stockroom shall be repaired.
06/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The exit sign located at the north mall exit shall be repaired.
06/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The exit sign located at the stockroom entrance shall be repaired.
06/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 The aisles in the stockroom shall be maintained free from obstructions.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00856
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/08/2005 INSP - FULL TKNAPP Approved