Case: T05FR00834
Case Details
Entered Date:
06/09/2005
Applicant:
BAILEY & BAILEY
Description:
Inspection
Outstanding Inspections
Case Number: T05FR00834
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 06/09/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TBC 110.1- No building shall be occupied without obtaining a Certificate of Occupancy from the building official. |
| 06/09/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 105.6.17- An operational permit shall be obtained to use, store and handle Class 3-B liquids in excess of 60 gallons. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00834
Case Description: INSPECTION
Total Completed Inspections - 17
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2005 | VIOL - WELDING & OTHER HOT WRK | JVALENZU | Approved | portable welding curtains have been purchased and available around workstation |
| 06/09/2005 | VIOL - WELDING & OTHER HOT WRK | JLANGEJA | Approved | TFC 2604.1.1- Hot work areas shall not contain combustibles or shall be provided with appropriate shielding. |
| 06/09/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JVALENZU | Approved | |
| 06/09/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Approved | TFC 2703.5.1- Containers with hazardous materials shall be clearly marked in an approved manner. 1. drum outside 2. solvent containers inside 3. waste oil tank |
| 06/09/2005 | VIOL - COMPRESSED GASES | JVALENZU | Approved | |
| 06/09/2005 | VIOL - COMPRESSED GASES | JLANGEJA | Approved | TFC 3003.3- Compressed gas cylinders shall be secured. 1. acetylene in S cage 2. CO in welding area |
| 06/09/2005 | VIOL - FIRE SERVICE FEATURES | JVALENZU | Approved | |
| 06/09/2005 | VIOL - FIRE SERVICE FEATURES | JLANGEJA | Approved | TFC 504.2- Doors that have been rendered non-functional shall be marked on the exterior side with the words THIS DOOR BLOCKED in letters 6" in height on a contrasting background. (W roll-up door) |
| 06/09/2005 | VIOL - FIRE PROTECTION SYSTEMS | JVALENZU | Approved | |
| 06/09/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Approved | TFC 906.7- Fire extinguishers shall be installed on hanger or bracket. |
| 06/09/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Approved | TFC 901.6- Fire extinguishers shall be serviced annually. |
| 06/09/2005 | VIOL - PRECAUTION AGAINST FIRE | JVALENZU | Approved | |
| 06/09/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Approved | TFC 315.2.1- Combustible storage shall be maintained at least 24" below the ceiling in unsprinklered buildings. (over office area) |
| 06/09/2005 | VIOL - FIRE RESIST.RATED CONST | JVALENZU | Approved | |
| 06/09/2005 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Approved | TFC 703.1- The required fire-resistive construction shall be maintained. 1. Crawl space access holes over office area 2. W outside porch area |
| 06/09/2005 | VIOL - BUILDING SVCS & SYSTEMS | JVALENZU | Approved | |
| 06/09/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Approved | TFC 605.5- Extension cords shall not be used as a substitute for permanent wiring. (computer room, N wall) |