Case: T05FR00772
Case Details
Entered Date:
05/25/2005
Applicant:
DND NEFFSON CO
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00772
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/25/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage in the stockroom shall be maintained 18 inches below the level of the sprinkler heads. |
05/25/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 The portable fire extinguisher located in the stockroom shall be inspected and tagged annually. |
05/25/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.5 The emergency illumination lights located on the sales floor and in the stockroom shall be repaired. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00772
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2005 | INSP - FULL | TKNAPP | Approved |