Case: T05FR00763
Case Details
Entered Date:
05/25/2005
Applicant:
DND NEFFSON CO
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00763
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/25/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 305.1 Clearance shall be provided between electrical equipment and combustible storage. Boxes stored against electrical transformer shall be moved. |
05/25/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage located in stockroom shall be maintained 18 inches below the level of the sprinkler heads. |
05/25/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The missing and broken celing tiles located in the stockroom shall be replaced or repaired. |
05/25/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.7 The extinguisher located in the stockroom shall be mounted on a hanger or bracket. |
05/25/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1013.4.1 Aisles located in the stockroom shall be maintained no less than 28 inches in width. |
05/25/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 The exit sign located at the south stockroom exit door shall be repaired so that it remains lit at all times. |
05/25/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 Aisles located in the stockroom shall be continuously maintained free from obstructions. Boxes shall not block aisles. |
05/25/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 The exit doorway located in the stockroom shall be continuously maintained free from obstructions. Width of the doorway shall be maintained clear. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00763
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/21/2005 | INSP - FULL | TKNAPP | Approved |