End Date Description Inspector Results Comments
05/25/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 305.1 Clearance shall be provided between electrical equipment and combustible storage. Boxes stored against electrical transformer shall be moved.
05/25/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage located in stockroom shall be maintained 18 inches below the level of the sprinkler heads.
05/25/2005 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 The missing and broken celing tiles located in the stockroom shall be replaced or repaired.
05/25/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 906.7 The extinguisher located in the stockroom shall be mounted on a hanger or bracket.
05/25/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1013.4.1 Aisles located in the stockroom shall be maintained no less than 28 inches in width.
05/25/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The exit sign located at the south stockroom exit door shall be repaired so that it remains lit at all times.
05/25/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 Aisles located in the stockroom shall be continuously maintained free from obstructions. Boxes shall not block aisles.
05/25/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 The exit doorway located in the stockroom shall be continuously maintained free from obstructions. Width of the doorway shall be maintained clear.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00763
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/21/2005 INSP - FULL TKNAPP Approved