Description:

inspection

Outstanding Inspections

Case Number: T05FR00739
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
05/23/2005 INSP - FULL EGRIFFIN Violation 1). Currently no fire extinguisher is present during hot work. TFC requires; 2604.2.6 Fire extinguisher. A minimum of one portable fire extinguisher complying with Section 906 and with a minimum 2-A: 20-BC rating shall be readily accessible within 30 feet (9144 mm) of the location where hot work is performed.
05/23/2005 VIOL - FIRE RESIST.RATED CONST EGRIFFIN Violation 2). Section of drywall is missing, this shall be repaired with proper and approved fire resistive construction. TFC 703.1