Case: T05FR00739
Case Details
Entered Date:
05/23/2005
Applicant:
RODGERS RICH SOUTH INC 50% & RRN INC 25% &
Description:
inspection
Outstanding Inspections
Case Number: T05FR00739
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/23/2005 | INSP - FULL | EGRIFFIN | Violation | 1). Currently no fire extinguisher is present during hot work. TFC requires; 2604.2.6 Fire extinguisher. A minimum of one portable fire extinguisher complying with Section 906 and with a minimum 2-A: 20-BC rating shall be readily accessible within 30 feet (9144 mm) of the location where hot work is performed. |
05/23/2005 | VIOL - FIRE RESIST.RATED CONST | EGRIFFIN | Violation | 2). Section of drywall is missing, this shall be repaired with proper and approved fire resistive construction. TFC 703.1 |