Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/20/2005

Applicant:

DND NEFFSON CO

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR00738
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
05/20/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage located in the east stockroom shall be maintained 18 inches below the level of the sprinkler heads.
05/20/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage located in the restroom shall be maintained 18 inches below the level of the sprinkler heads.
05/20/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 Sprinkler heads shall not be obstructed by merchandise. The large framed picture hanging from the sales floor ceiling near the sprinkler head shall be moved.
05/20/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1011.1 The exit sign located in the sales room near the rear southeast exit shall not be obstructed.
05/20/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The 2 exit signs located at the south east exit shall be repaired so that they remain lit at all times.
05/20/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The exit sign located at the north mall exit shall be repaired so that it remains lit at all times.
05/20/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 The rear southeast exit shall not be obstructed.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00738
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/07/2005 INSP - FULL TKNAPP Approved