Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR00722
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
05/19/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage in childrens shoe stockroom shall be maintained 18 inches below the level of the sprinkler heads.
05/19/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage in mens shoe stockroom shall be maintained 18 inches below the level of the sprinkler heads.
05/19/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage in womens fitness stockroom shall be maintained 18 inches below the level of the sprinkler heads.
05/19/2005 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 The missing ceiling tiles located in the housewares area mens stockroom shall be replaced.
05/19/2005 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 The missing ceiling tiles located in the janitors closet shall be replaced.
05/19/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8 The exit door located in the receiving area shall be openable from the egress side without the use of a key.
05/19/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1013.4.1 Clear aisles shall be maintained in stockrooms throughout the store.
05/19/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1013.4.1 Clear aisles shall be maintained in the cosmetics stockroom.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00722
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/02/2005 INSP - FULL TKNAPP Approved