Full Inspection

Outstanding Inspections

Case Number: T05FR00678
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 17
End Date Description Inspector Results Comments
05/13/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.3 The electrical equipment room across from the salon shall not be used for storage.
05/13/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 The electrical panels located near the box compactor shall have a 3 oot deep clear space in front of them.
05/13/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 The electrical cord for the fluorescent light fixtures located in the luggage area of the stockroom shall not extend through the doorway nearby.
05/13/2005 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 The missing ceiling tile located in the old alterations room off the womens dressing room shall be replaced.
05/13/2005 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 The missing ceiling tile located in the salons stockroom shall be replaced.
05/13/2005 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 The missing ceiling tile located in the southwest exit corridor near the womens clothing area shall be replaced.
05/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8 The exit door located in the receiving area shall not be equipped with a lock requiring a key or special knowledge.
05/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.3 A sign shall be posted at the ground level exit doors leading outside (south Wetmore side and west Oracle side) stating: This door to remain unlocked when building is occupied.
05/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The exit sign located at the bottom of the stairway from the 2nd exit in the mens suites area shall be repaired so that it remains lit at all times.
05/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The exit sign located at the bottom of the stairway from the exit in the mens suites area shall be repaired so that it remains lit at all times.
05/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The exit sign located at the bottom of the stairway near the passenger elevator shall be repaired so that it remains lit at all times.
05/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 The cardboard sign located at the bottom of the stairway near the passenger elevator shall be removed from the exit doors.
05/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 The childrens clothing rack located directly in front of the exit doors in the childrens clothing area shall be moved to provide a clear space in front of the doors.
05/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 The exit corridor from the childrens clothing area to the southwest exit doors shall not be used for storage. Storage shall be removed from this corridor.
05/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 The exit corridor from the womens clothing area to the southwest exit door shall not be used for storage.
05/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 The mens shirt rack located directly in front of the exit doors near the east mall exit shall be moved to provide a clear space in front of doors.
05/13/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 The womens clothing rack located directly in front of the exit doors in the womens clothing area shall be moved to provide a clear space in front of the doors.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00678
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/08/2005 INSP - FULL TKNAPP Approved