Case Number: T05FR00678
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 17
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/13/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.3 The electrical equipment room across from the salon shall not be used for storage. |
| 05/13/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 The electrical panels located near the box compactor shall have a 3 oot deep clear space in front of them. |
| 05/13/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 The electrical cord for the fluorescent light fixtures located in the luggage area of the stockroom shall not extend through the doorway nearby. |
| 05/13/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The missing ceiling tile located in the old alterations room off the womens dressing room shall be replaced. |
| 05/13/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The missing ceiling tile located in the salons stockroom shall be replaced. |
| 05/13/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The missing ceiling tile located in the southwest exit corridor near the womens clothing area shall be replaced. |
| 05/13/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 The exit door located in the receiving area shall not be equipped with a lock requiring a key or special knowledge. |
| 05/13/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8.3 A sign shall be posted at the ground level exit doors leading outside (south Wetmore side and west Oracle side) stating: This door to remain unlocked when building is occupied. |
| 05/13/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 The exit sign located at the bottom of the stairway from the 2nd exit in the mens suites area shall be repaired so that it remains lit at all times. |
| 05/13/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 The exit sign located at the bottom of the stairway from the exit in the mens suites area shall be repaired so that it remains lit at all times. |
| 05/13/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 The exit sign located at the bottom of the stairway near the passenger elevator shall be repaired so that it remains lit at all times. |
| 05/13/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 The cardboard sign located at the bottom of the stairway near the passenger elevator shall be removed from the exit doors. |
| 05/13/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 The childrens clothing rack located directly in front of the exit doors in the childrens clothing area shall be moved to provide a clear space in front of the doors. |
| 05/13/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 The exit corridor from the childrens clothing area to the southwest exit doors shall not be used for storage. Storage shall be removed from this corridor. |
| 05/13/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 The exit corridor from the womens clothing area to the southwest exit door shall not be used for storage. |
| 05/13/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 The mens shirt rack located directly in front of the exit doors near the east mall exit shall be moved to provide a clear space in front of doors. |
| 05/13/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 The womens clothing rack located directly in front of the exit doors in the womens clothing area shall be moved to provide a clear space in front of the doors. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00678
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2005 | INSP - FULL | TKNAPP | Approved |