Case: T05FR00642
Case Details
Entered Date:
05/09/2005
Applicant:
NORVILLE ALLAN J & ALFENA A
Description:
Inspection
Outstanding Inspections
Case Number: T05FR00642
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/27/2005 | INSP - FULL | WCUMMING | Violation | This occupancy is vacant and being remodeled. |
| 04/27/2005 | VIOL - FIRE PROTECTION SYSTEMS | WCUMMING | Correction Required | TFC 901.6.1 Fire protection systems shall be inspected annually, tested annually, and maintained. (Last test date - 2/27/03) |
| 04/27/2005 | VIOL - MEANS OF EGRESS | WCUMMING | Correction Required | TFC 1011 Exits signs shall be viewable and operational at all times. The rear exit sign needs to be repaired. |