Case: T05FR00622
Case Details
Entered Date:
05/05/2005
Applicant:
AVITIA YOLONDA V
Description:
VANS Inspection
Outstanding Inspections
Case Number: T05FR00622
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/05/2005 | INSP - FULL | GDAURIA | Violation | VANS |
05/05/2005 | VIOL - ADMINISTRATION | GDAURIA | Correction Required | 110.1.1 Unsafe conditions. Fill or protect large open sewer excavation on west side |
05/05/2005 | VIOL - ADMINISTRATION | GDAURIA | Correction Required | 110.1.2 Structural hazards. Front portico dilapidated and unstable. should be shored or demolished |
05/05/2005 | VIOL - ADMINISTRATION | GDAURIA | Correction Required | 110.4 Abatement. The owner, operator, or occupant of a building or premises deemed unsafe by the fire code official shall abate or cause to be abated or corrected such unsafe conditions either by repair, rehabilitation, demolition or other approved corrective action. Address condition of front portico |
05/05/2005 | VIOL - PRECAUTION AGAINST FIRE | GDAURIA | Correction Required | 311.2.1 Security. Exterior openings and interior openings accessible to other tenants or unauthorized persons shall be boarded, locked, blocked or otherwise protected to prevent entry by unauthorized individuals. Adequate fencing required |