Case: T05FR00598
Case Details
Entered Date:
05/04/2005
Applicant:
DND NEFFSON CO
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00598
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 18
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/04/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2 Storage of combustible materials in the fragrance stockroom shall be orderly. |
05/04/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2 Storage of combustible materials in the visual room shall be orderly. |
05/04/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage located in the visual room shall be maintained 18 inches below the level of the sprinkler head. |
05/04/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage of large signs in womens shoe stockroom on top of shelfs shall be removed so as not to block flow of sprinkler heads. |
05/04/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.2 The stairways near the executive offices on the 2nd floor and at the employee entrance at the first floor shall not be used for the storage of combustible materials. |
05/04/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.3 The electrical room near the maintenance room shall not be used for storage. |
05/04/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 The electrical panel (2HB) located in the visual room closet shall have blanks installed to replace space caused by missing breakers. |
05/04/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The junction box located in the video room near the mens clothing area shall have an approved cover. |
05/04/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction box located in the visual room closet shall have an approved cover. |
05/04/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The missing ceiling tiles in the closet by the executive office shall be replaced. |
05/04/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The missing ceiling tiles in the Equipment room near the glass room shall be replaced. |
05/04/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The missing ceiling tiles in the mens woven clothing fixture room shall be replaced. |
05/04/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The missing ceiling tiles in the ready to ware petite stockroom shall be maintained 18 inches below the level of the sprinkler heads. |
05/04/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The missing ceiling tiles in the salon fixture room shall be replaced. |
05/04/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The missing ceiling tiles in the small office near the cash office shall be replaced. |
05/04/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The missing ceiling tiles in the tommy hilfiger stockroom shall be replaced. |
05/04/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1013.4.1 A clear aisle width shall be maintained in the fragrance stockroom. |
05/04/2005 | VIOL - FLAMMABLE LIQUIDS | TKNAPP | Correction Required | 3404.3.2.1.3 The doors to the liquid storage cabinet located in the visual room shall be kept closed. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00598
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/19/2005 | INSP - FULL | TKNAPP | Approved |