Case: T05FR00597
Case Details
Entered Date:
05/04/2005
Applicant:
MC DONALD S CORPORATION
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00597
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage shall be 18 inches below celing. |
| 05/04/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 A cover shall be provided for fluorescent fixtures in basement. |
| 05/04/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Large junction box in closet off break room shall have an approved cover. |
| 05/04/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.5 A class K extinguisher shall be within 30 feet of the comercial cooking equipment. |
| 05/04/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1006.1 The means of egress shall be illuminated at all times. Illumination shall be installed in dining room, kitchen, basement, and stairway. |
| 05/04/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 The rear west side exit shall not be equipped with a lock that requires a key. |
| 05/04/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.9 The panic hardware on the northwest door shall be repaired. |
| 05/04/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1011.1 Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Exit signs shall be posted at all building exits. |
| 05/04/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1011.2 Exit signs shall be illuminated. |
| 05/04/2005 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3 Compressed gas cylinder in basement shall be secured to prevent it from falling. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00597
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2005 | INSP - FULL | TKNAPP | Approved |