Inspection

Outstanding Inspections

Case Number: T05FR00593
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
05/03/2005 VIOL - ADMINISTRATION JLANGEJA Violation TBC 110.1- No building or structure shall be used or occupied...until the building official has issued a Certificate of Occupancy.
05/03/2005 VIOL - FIRE SERVICE FEATURES JLANGEJA Violation TFC 504.2- Exterior doors that have been rendered non-functional...shall have a sign affixed to the exterior side of the door stating "THIS DOOR BLOCKED" with 6" letters on contrasting background.
05/03/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Identified electrical hazards shall be abated. The opening in the wall shall be covered.
05/03/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring.
05/03/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers shall be serviced annually.