Case: T05FR00588
Case Details
Entered Date:
05/02/2005
Applicant:
BAYVIEW ASSOCIATES
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00588
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 603.2 Metal chimney for hot water heater shall be repaired. |
05/02/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.5 A class K portable fire extinguisher shall be provided within 30 feet of commercial cooking. |
05/02/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.7 Portable fire extinguisher in back room shall be installed on a hanger. |
05/02/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.6 The panic hardware on the rear door shall be the only locking device on the door. Deadbolt lock shall be removed. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00588
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/18/2005 | INSP - FULL | TKNAPP | Approved |