Description:

Correction to sprinkler coverage

Outstanding Inspections

Case Number: T05FR00587
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
05/02/2005 VIOL - FIRE PROTECTION SYSTEMS CSCHULTZ Violation TFC 901 Fire protection systems. Fire sprinkler systems shall be maintained at all times & sprinkler coverage shall be maintained at all times. 1.) Shall correct sprinkler coverage in dinning room by wall separating dinning room and service area. 2.) Shall correct sprinkler coverage in service area hallway go to dinning room. 3.) Shall move lights away from sprinkler heads in service area.