Case Number: T05FR00579
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date Description Inspector Results Comments
04/29/2005 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 505.1 Address numbers shall be posted in accordance with Pima County address standards.
04/29/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 Electrical panels in the bakery shall have a clear working space.
04/29/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 Electrical panels located by the south east stockroom exit door shall have a 3 foot deep clear working space.
04/29/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3.1 A sign stating ELECTRICAL ROOM shall be posted on electrical room door.
04/29/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3/315.2 Electrical room shall not be used for storage.
04/29/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 Extinsion cord in bakery shall be removed.
04/29/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 Extinsion cord located at the recieving desk area shall be removed.
04/29/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 Open junction box in the freezer shall have an approved cover.
04/29/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The electrical outlets in the southeast corner of the managers office and in the breakroom on the south wall shall have approved covers.
04/29/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.6.3 The hood vent system in the bakery shall be cleaned.
04/29/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The exit sign at the south east exit door shall be lit at all times.
04/29/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.3 The southwest exit doors shall be free from obstructions.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00579
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/26/2005 INSP - FULL TKNAPP Approved