Case Number: T05FR00556
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/28/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage in stockroom behind main stockroom shall be maintained 18 inches below sprinkler heads. |
04/28/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 A 36 inch working space shall be maintained in front of electrical panels in electrical room. |
04/28/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction box located in the upstairs stockroom shall have an approved cover. |
04/28/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Fire extinguisher in elevator machine room shall be inspected annually. |
04/28/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Fire extinguisher in north projection room shall be inspected annually. |
04/28/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 The sprinkler piping in stockroom 8 shall be secured and nothing shall be hung on piping. |
04/28/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.7 Portable fire extinguisher in north projection room shall be installed on a hanger. |
04/28/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1007.1 The elevator is a required accessible means of egress for the wheelchair spaces in theaters 10 and 11. Untill the elevator is in proper working condition, customers requiring wheelchairs shall not be allowed to use these spaces. These customers can use the ground level spaces. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00556
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/11/2005 | INSP - FULL | TKNAPP | Approved |