Case Number: T05FR00530
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
04/26/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 102.4- Repairs, alterations and additions to existing structures shall comply with the IBC. TBC 110.1- A Certificate of Occupancy shall be obtained from Development Services @ 201 N Stone.
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space of 30' width x 36" depth x 78" height shall be provided in front of electrical service equipment.
04/26/2005 VIOL - FIRE RESIST.RATED CONST JLANGEJA Violation TFC 703.1- Openings made for passage of electrical conduit and wires shall be protected with approved means capable of resisting the passage of smoke and fire.
04/26/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers shall be serviced annually.
04/26/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 907.6- Fire extinguishers shall be installed on their hanger or bracket and be securely anchored.
04/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1018.3- Exits shall be continuous from the point of entry into the exit to the exit discharge.
04/26/2005 VIOL - WELDING & OTHER HOT WRK JLANGEJA Violation TFC 2604.1.5- Partitions segregating hot work areas...shall be non-combustible. In fixed hot work areas, the partitions shall be securely connected to the floor such that no gap exists between the floor and the partition.
04/26/2005 VIOL - WELDING & OTHER HOT WRK JLANGEJA Violation TFC 2606.4- The emergency disconnect shall be marked "EMERGENCY DISCONNECT" and shall be visible from the equipment.
04/26/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.5.1- Individual containers, cartons and packages shall be conspicuously marked or labeled in an approved manner.
04/26/2005 VIOL - COMPRESSED GASES JLANGEJA Violation TFC 3003.3- Compressed gas cylinders shall be secured against accidental dislodgement.