Case: T05FR00530
Case Details
Entered Date:
04/26/2005
Applicant:
COX MASONRY INC
Description:
Inspection
Outstanding Inspections
Case Number: T05FR00530
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 04/26/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 102.4- Repairs, alterations and additions to existing structures shall comply with the IBC. TBC 110.1- A Certificate of Occupancy shall be obtained from Development Services @ 201 N Stone. |
| 04/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of 30' width x 36" depth x 78" height shall be provided in front of electrical service equipment. |
| 04/26/2005 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | TFC 703.1- Openings made for passage of electrical conduit and wires shall be protected with approved means capable of resisting the passage of smoke and fire. |
| 04/26/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be serviced annually. |
| 04/26/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 907.6- Fire extinguishers shall be installed on their hanger or bracket and be securely anchored. |
| 04/26/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1018.3- Exits shall be continuous from the point of entry into the exit to the exit discharge. |
| 04/26/2005 | VIOL - WELDING & OTHER HOT WRK | JLANGEJA | Violation | TFC 2604.1.5- Partitions segregating hot work areas...shall be non-combustible. In fixed hot work areas, the partitions shall be securely connected to the floor such that no gap exists between the floor and the partition. |
| 04/26/2005 | VIOL - WELDING & OTHER HOT WRK | JLANGEJA | Violation | TFC 2606.4- The emergency disconnect shall be marked "EMERGENCY DISCONNECT" and shall be visible from the equipment. |
| 04/26/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.5.1- Individual containers, cartons and packages shall be conspicuously marked or labeled in an approved manner. |
| 04/26/2005 | VIOL - COMPRESSED GASES | JLANGEJA | Violation | TFC 3003.3- Compressed gas cylinders shall be secured against accidental dislodgement. |