Case: T05FR00514
Case Details
Entered Date:
04/21/2005
Applicant:
CARPENTERS UNION 408
Description:
FULL INSPECTION
Outstanding Inspections
Case Number: T05FR00514
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| VIOL - PRECAUTION AGAINST FIRE | None | Not Inspected | ||
| VIOL - MEANS OF EGRESS | None | Not Inspected | ||
| 04/21/2005 | INSP - FULL | FCONTRER | Correction Required | TFC 105.3.5 Need to post the business Lic. and Cof O permits. TFC 1004.3 Need to post the occupant load sign.This is for the assembly room. TFC 1011.2 Basement area exit signs need to be illuminated,replace burned out light bulbs in the exit signs.TFC 315.2 Housekeeping in the rooms behind stage area. TFC 1003.6 egress continuity: west exit door leading outside next to the stage, is enclosed with a fence,need to remove or make a exit path away from the building. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00514
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2005 | VIOL - ADMINISTRATION | FCONTRER | Approved |