Case: T05FR00510
Case Details
Entered Date:
04/21/2005
Applicant:
EWING WILLIAM M & LORETTA JT/RS
Description:
Inspection
Outstanding Inspections
Case Number: T05FR00510
Case Status: REFERRED
Case Description: INSPECTION
Total Outstanding Inspections - 9
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 04/21/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 110.1- No building or structure shall be occupied or used...until the building official has issued a Certificate of Occupancy |
| 04/21/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.1- Storage of combustibles shall be maintained 2 feet or more below ceiling in a non-sprinklered building. |
| 04/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.1- Identified electrical hazards shall be abated. Electrical panel shall have blanks installed in voids. |
| 04/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.1- The overhead light fixture shall be properly connected in accordance to the ICC Electrical Code. |
| 04/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of 30"x 36" x 78" shall be provided in front of electrical service equipment. |
| 04/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (overhead to light fixture, office) |
| 04/21/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be inspected monthly and tested annually. |
| 04/21/2005 | VIOL - LUMBER YARD & WOOD FAC. | JLANGEJA | Violation | TFC 1903.2- Equipment inside buildings which generate or emits combustible dust shall be provided with an approved dust collection and exhaust system. |