Case Details

Status:

REFERRED

Type:

INSPECTION
Address:

Entered Date:

04/21/2005

Applicant:

EWING WILLIAM M & LORETTA JT/RS

Description:

Inspection

Outstanding Inspections

Case Number: T05FR00510
Case Status: REFERRED
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
04/21/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 110.1- No building or structure shall be occupied or used...until the building official has issued a Certificate of Occupancy
04/21/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.1- Storage of combustibles shall be maintained 2 feet or more below ceiling in a non-sprinklered building.
04/21/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Identified electrical hazards shall be abated. Electrical panel shall have blanks installed in voids.
04/21/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- The overhead light fixture shall be properly connected in accordance to the ICC Electrical Code.
04/21/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space of 30"x 36" x 78" shall be provided in front of electrical service equipment.
04/21/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (overhead to light fixture, office)
04/21/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers shall be inspected monthly and tested annually.
04/21/2005 VIOL - LUMBER YARD & WOOD FAC. JLANGEJA Violation TFC 1903.2- Equipment inside buildings which generate or emits combustible dust shall be provided with an approved dust collection and exhaust system.