Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T05FR00499
Case Details
Entered Date:
04/15/2005
Applicant:
DEVELOPMENT TRADING AND TRANSACTING
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00499
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Light fixture in the produce cooler shall be repaired |
04/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 The electrical panels in the deli storage room shall be accessable |
04/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.4/605.5 Multiplug adapters shall be removed from florist work area, extension cords shall not be used as permanent wiring. |
04/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extension cord in deli for small water cooler shall not be used as permanent wiring |
04/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The junction box located above the walk in freezer door shall be repaired |
04/15/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11 The commercial cooking system extinguishing system shall be repaired |
04/15/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.4 The commercial cooking system shall be inspected every 6 months |
04/15/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit sign at NW exit shall be illuminated |
04/15/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit sign at the south exit shall be illuminated at all times |
04/15/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 Stairway leading to the motor room shall be maintained clear and not used for storage |
04/15/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.6 Where panic hardware is installed it shall be the only locking device on the door, lock shall be removed from recieving door |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00499
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/30/2005 | INSP - FULL | TKNAPP | Approved |