Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/15/2005

Applicant:

DEVELOPMENT TRADING AND TRANSACTING

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR00499
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
End Date Description Inspector Results Comments
04/15/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 Light fixture in the produce cooler shall be repaired
04/15/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 The electrical panels in the deli storage room shall be accessable
04/15/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.4/605.5 Multiplug adapters shall be removed from florist work area, extension cords shall not be used as permanent wiring.
04/15/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 Extension cord in deli for small water cooler shall not be used as permanent wiring
04/15/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The junction box located above the walk in freezer door shall be repaired
04/15/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11 The commercial cooking system extinguishing system shall be repaired
04/15/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.6.4 The commercial cooking system shall be inspected every 6 months
04/15/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit sign at NW exit shall be illuminated
04/15/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit sign at the south exit shall be illuminated at all times
04/15/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 Stairway leading to the motor room shall be maintained clear and not used for storage
04/15/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.6 Where panic hardware is installed it shall be the only locking device on the door, lock shall be removed from recieving door

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00499
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/30/2005 INSP - FULL TKNAPP Approved