Case Number: T05FR00482
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
04/14/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 110.1- No building or structure shall be occupied...until the building official has issued a Certificate of Occupancy. A C of O can be obtained at Development Services, 201 N Stone.
04/14/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring.
04/14/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers shall be inspected monthly and serviced annually.
04/14/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.7- Fire extinguishers shall be mounted on their hanger or bracket.
04/14/2005 VIOL - WELDING & OTHER HOT WRK JLANGEJA Violation TFC 2604.2.6- A fire Extinguisher with a minimum 2-A:20-B:C rating shall be readily accessible within 30' of where hot work is performed.
04/14/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.9.8- Incompatible materials shall be separated by a minimum of 20'. Flammables and combustibles shall be separated from hot work areas.