Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/13/2005

Applicant:

CONCANNON MATTHEW J

Description:

Fire Inspection

Outstanding Inspections

Case Number: T05FR00477
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
04/13/2005 VIOL - FIRE PROTECTION SYSTEMS JDAVIS Correction Required Proviedd two fire extiguishers; They shab be at leaset 2A10BC and shall be seviced annually and properly mounted.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00477
Case Description: INSPECTION
Total Completed Inspections - 3
End Date Description Inspector Results Comments
04/13/2005 VIOL - BUILDING SVCS & SYSTEMS JDAVIS Approved 605.3 Provide a deadface panel on you electrical box outside (rear)
04/13/2005 VIOL - BUILDING SVCS & SYSTEMS JDAVIS Approved 606.6 Abate electrical hazards: A. Exposed wires: -West wall: romex is currently spliced to light -exposed wires in the conduit going to the the light (loft) -open j-box outside the old spray booth -light fixture outside the old spay booth. Note: Booth is no longer operable. Absolutely no spraying is allowed at any time in the old booth.
04/13/2005 VIOL - FIRE SERVICE FEATURES JDAVIS Approved 505.1 Provide proper addressing (12")