Case: T05FR00462
Case Details
Entered Date:
04/06/2005
Applicant:
OLYMPIC VIEW PROPERTIES INC
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00462
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extension cords shall not be a substitute for permanant wiring |
| 04/06/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8.4 Flush bolts on northwest door shall be removed. |
| 04/06/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit sign at west sales floor door shall be illuminated. |
| 04/06/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 West exit door shall be uncovered, and free from obstructions. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00462
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2005 | INSP - FULL | TKNAPP | Approved |