Applicant:

MENLO PARK SHOPPING CENTER COMPANY

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR00428
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date Description Inspector Results Comments
03/30/2005 VIOL - ADMINISTRATION TKNAPP Correction Required Tucson Spa/Pool code sec. 717.6 All pool gates shall close and latch automatically.
03/30/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 The electrical panels at building F, E, B, and on the main building shall be secured to the building.
03/30/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 The flourescent light in the laundry room shall be repaired.
03/30/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 A clear working space of 36" shall be maintained in front of the electrical panels in the laundry room.
03/30/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The junction boxes located in the SW storage room (Building F), SW corner of building B, in the laundry room on the north wall,and on the rear of the dryers in the laundry room, shall have covers.
03/30/2005 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 The attic access opening in the small kitchen shall have a door.
03/30/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 The "K" class extinguisher in the kitchen shall be inspected annually.
03/30/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.1 The manual actuation device for the hood system in the kitchen shall be relocated so that it is at least 10 feet away from the system.
03/30/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8 The egress doors from the kitchen shall be readily openable from the kitchen side without a key.
03/30/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1011.1 Illuminated exit signs shall be provided for the 2 lounge exits.
03/30/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.3 The east door from the dining room shall be fully openable.
03/30/2005 VIOL - COMPRESSED GASES TKNAPP Correction Required 3003.3 The compressed gas cylinders in the kitchen shall be secured to prevent them from falling.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00428
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/05/2005 INSP - FULL TKNAPP Approved