Case: T05FR00428
Case Details
Entered Date:
03/30/2005
Applicant:
MENLO PARK SHOPPING CENTER COMPANY
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00428
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/30/2005 | VIOL - ADMINISTRATION | TKNAPP | Correction Required | Tucson Spa/Pool code sec. 717.6 All pool gates shall close and latch automatically. |
03/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 The electrical panels at building F, E, B, and on the main building shall be secured to the building. |
03/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 The flourescent light in the laundry room shall be repaired. |
03/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 A clear working space of 36" shall be maintained in front of the electrical panels in the laundry room. |
03/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The junction boxes located in the SW storage room (Building F), SW corner of building B, in the laundry room on the north wall,and on the rear of the dryers in the laundry room, shall have covers. |
03/30/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The attic access opening in the small kitchen shall have a door. |
03/30/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 The "K" class extinguisher in the kitchen shall be inspected annually. |
03/30/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.1 The manual actuation device for the hood system in the kitchen shall be relocated so that it is at least 10 feet away from the system. |
03/30/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 The egress doors from the kitchen shall be readily openable from the kitchen side without a key. |
03/30/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1011.1 Illuminated exit signs shall be provided for the 2 lounge exits. |
03/30/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.3 The east door from the dining room shall be fully openable. |
03/30/2005 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3 The compressed gas cylinders in the kitchen shall be secured to prevent them from falling. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00428
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/05/2005 | INSP - FULL | TKNAPP | Approved |