Case: T05FR00409
Case Details
Entered Date:
03/28/2005
Applicant:
HANSEN JORGEN V TR 1/3 &
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00409
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.3 Storage shall be removed from the closet at the east side sprinkler riser. |
| 03/28/2005 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 510.1 The east side sprinkler riser closet shall be identified with a sign stating "Sprinkler Riser". |
| 03/28/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 The electrical panel in the stockroom shall have a clear working space maintained for access. |
| 03/28/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 The fire sprinkler system shall be inspected annually, Last tag stated 4-2002. |
| 03/28/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 The portable fire extinguisher located at the northwest corner storage room exit shall be inspected and tagged. |
| 03/28/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6/ 605.1 The electrical wiring located at the sprinkler riser near the loading dock shall be repaired. |
| 03/28/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit signs at the northwest corner storage room and at the west of the salesfloor shall be internally lit at all times. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00409
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2005 | INSP - FULL | TKNAPP | Approved |