Case Number: T05FR00408
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
03/28/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 Electrical panels in northeast corner of store shall have a clear working space of 36 inches deep and the width of the panels.
03/28/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 906.6 The fire extinguisher in the northeast corner of the stockroom shall not be obscured.
03/28/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 Exit access at the southeast exit shall be maintained free from obstructions.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00408
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/12/2005 INSP - FULL TKNAPP Approved