Case: T05FR00370
Case Details
Entered Date:
03/15/2005
Applicant:
SHENITZER DEVELOPMENT LIMITED LIABILITY
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00370
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/15/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2 Storage shall be maintained 18 inches below sprinkler heads. |
03/15/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.3.1 Combustible materials shall not be stored under nonsprinklered canopy at the rear loading dock. |
03/15/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Portable fire extinguishers shall be inspected annually. |
03/15/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1006.1 Emergency egress light in the north stockroom shall be repaired. |
03/15/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.1 An exit door shall be maintained on the east side of the southeast stockroom. |
03/15/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.1 Two exit doors shall be maintained from the north stockroom. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00370
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/24/2005 | INSP - FULL | TKNAPP | Approved |