Case: T05FR00367
Case Details
Entered Date:
03/11/2005
Applicant:
PANTANO-ESCALANTE ASSOCIATES LLC
Description:
full inspection
Outstanding Inspections
Case Number: T05FR00367
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| VIOL - BUILDING SVCS & SYSTEMS | None | Not Inspected | ||
| VIOL - FIRE PROTECTION SYSTEMS | None | Not Inspected | ||
| 03/11/2005 | INSP - FULL | FCONTRER | Correction Required | Closet need to remove combustables from heater.TFC-305.1 |
| 03/11/2005 | INSP - FULL | FCONTRER | Correction Required | Need to have fire drills TFC408.5.4. Test emergency lights TFC604.3. |
| 03/11/2005 | INSP - FULL | FCONTRER | Correction Required | TFC605 Electrical panel remove tape from breakers so the breakers can trip in an over load or short. |
| 03/11/2005 | INSP - FULL | FCONTRER | Correction Required | The fire protection system needs its annual test.TFC-901. |