Description:

Full Fire Inspection

Outstanding Inspections

Case Number: T05FR00307
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
03/02/2005 VIOL - FIRE SERVICE FEATURES SHIGGINB Violation Section 505.1 Address numbers. Address numbers shall be in accordance with Pima County address display requirements. 1. Adress must be posted on front and rear of building. Handout given
03/03/2005 VIOL - BUILDING SVCS & SYSTEMS SHIGGINB Violation ELECTRICAL EQUIPMENT, WIRING AND HAZARDS 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. 1. Storage room wall to close to electrial panel. Most have 36" cleaance in front of electrial panel. 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 1. Repair or replace electrial box and conduit on east wall of laundry room
03/03/2005 VIOL - BUILDING SVCS & SYSTEMS SHIGGINB Violation FUEL-FIRED APPLIANCES 603.7 Discontinuing operation of unsafe heating appliances. The fire code official is authorized to order that measures be taken to prevent the operation of any existing stove, oven, furnace, incinerator, boiler or any other heat-producing device or appliance found to be defective or in violation of code requirements for existing appliances after giving notice to this effect to any person, owner, firm or agent or operator in charge of the same. The fire code official is authorized to take measures to prevent the operation of any device or appliance without notice when inspection shows the existence of an immediate fire hazard or when imperiling human life. The defective device shall remain withdrawn from service until all necessary repairs or alterations have been made. 603.7.1 Unauthorized operation. It shall be a violation of this code for any person, user, firm or agent to continue the utilization of any device or appliance (the operation of which has been discontinued or ordered discontinued in accordance with Section 603.7), unless written authority to resume operation is given by the fire code official. Removing or breaking the means by which operation of the device is prevented shall be a violation of this code. 1. 24 ' cleance must be maintaned in front of gas manifold for maintance of burner and to protect the flow of gas from the jets to the burners. No storage of any kind shall be within this 24" clearnce.
03/03/2005 VIOL - FIRE PROTECTION SYSTEMS SHIGGINB Violation 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 1. Max. travel distance to fire extingusher is 75' 2. Tested and taged annunlly.
03/03/2005 VIOL - MEANS OF EGRESS SHIGGINB Violation 1013.2 Egress through intervening spaces. Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the area served; are not a high-hazard occupancy and provide a discernible path of egress travel to an exit. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. An exit access shall not pass through a room that can be locked to prevent egress. Means of egress from dwelling units or sleeping areas shall not lead through other sleeping areas, toilet rooms or bathrooms. 1. No exit through the laundry room. 2. All locks must be removed from door that are a part of the egress path.